Key points
- Rugged transducer arrangement
- Damped steady readings
- Overpressure warning light
- Lo-Bat indication
- Usable in case with hanging strap
- Pockets for tubing & adaptor storage
- Calibration certificate
|
 |
Suitable for Differential Pressure measurement across balancing valves,
orifice plates, chiller etc. in waterflow systems
Flow rate can be related to D.P. using individual valve charts/KV values.
All units are leak tested to 10 Bar and calibrated before despatch. The
unit comes complete with a calibration certificate, pair of binder adaptors
and a padded carry case.
The instrument can be used in the carry case,
the strap having a quick release break in the middle so it can be used
as a hanging strap or loop around pipe work. There is a back pocket arrangement
for storage of the nylon tubing & female adaptors.
Simple to use, just turn on, zero, connect, flush and close valve to
read.
Providing the line pressure does not exceed 10 Bar no damage can be done to the transducer arrangement,
if one side
only is accidentally pressurised. If the static pressure is exceeded,
a warning light is illuminated.
Specification |
Value |
| Range |
0 – 199.9 KPa (last digit = 0.1 KPa) |
| Max.
Line pressure |
10 Bar G |
| Max. Single port overpressure |
10 Bar G |
| Accuracy |
+/- 0.3 Kpa or +/- 0.5%
whichever is greater |
| Operating temperature range |
0 – 50 DegC (at the transducer) |
| Battery Life |
100 hours
approx (2 x 9 volt PP3) |
| Transducer wetted parts |
stainless steel |
| Size & weight |
280 x 110
x 50 mm ; 0.9 KG |
| Calibration period |
12 months |
Storage : It is good practice to protect all instrumentation from frost,
but no damage should be encountered if the instrument is frozen and subsequently
thawed out.
Draft data sheet, Initial price will be £595.00 Nett,ex-works including pair Binder adaptors